Low Voltage Cable
Aluminum double insulated cable 0.6 / 1KV 2-3 conductors AL / XLPE / PVC
+ Cable for low voltage network, working voltage up to 0.6 / 1kV.
+ Applied standard: TCVN 5935-1: 2013.
+ Structure:
- Conductor: twisted braided from multiple hard aluminum strands.
- White XLPE insulated with natural color separation.
- Fillers, rolls: PP, PET, PVC.
- Protective casing with black PVC.
+ Rated voltage (Uo / U) 0.6 / 1kV.
Number of cores: 2x7 strands or 19 strands, or 3x7 strands or 19 strands or 37 strands.
+ Maximum conductor temperature in normal operation is 90 degrees Celsius
+ Nominal profile: From 11 mm2 to 240 mm2
Nominal cross section area |
Conductor |
Insulation thickness | Thickness of PVC sheath | App. overall diameter | Insulaion resistance at 70oC | App. weight wires | Packed lenght | |
No of wires |
Diameter |
|||||||
(mm) | (No.) | (mm) | (mm) | mm | (mm) | (V/min) | (Ω/km) | (m) |
2x11 | 7 | 1.40 | 0.7 | 1.3 | 18 | 3.080 | 0.289 | 2000 |
2x16 | 7 | 1.70 | 0.7 | 1.3 | 20 | 1.910 | 0.358 | 2000 |
2x25 | 7 | 2.13 | 0.9 | 1.3 | 24 | 1.200 | 0.507 | 2000 |
2x35 | 7 | 2.51 | 0.9 | 1.3 | 26 | 0.866 | 0.607 | 1000 |
2x50 | 7 | 3.00 | 1.0 | 1.4 | 29 | 0.641 | 0.779 | 1000 |